TECHNICAL DESCRIPTION
TESED SWITCHGEAR AND
CONTROLGEAR TYPE
ASSEMBLY
STANDARDAS/SPECIFICATION
IEC 60439-1 (1999), DIN EN
60439-1 (VDE 0660 PART 500)
CREEPAGE DISTANCES AND CLEARANC   RATED IMPULSE WITSTAND
VOLTAGE (Uimp)
8 KV
  OVERVOLTAGE CATEGORY III
  POLLUTION DEGREE 3
RATED INSULATION VOLTAGE (Ui)   1000 V
RATED OPERATION VOLTAGE (Ue)   UP TO 690 V
RATED CURRENTS (Ie)
BUS BAR STSTEM (3 PHASE 4 WIRES)
MAIN HORIZONTAL BUS BARS 
RATED CURRENT   7400A
RATED PAEK WITHSTAND CURRENT (Ipk)
 176 KA 
RATED SHORT-TIME WITHSTAND 
CURRENT (Icw) 80 KA, 1s
  VERTICAL BUS BARS FOR DISTRIBUTION
FEEDERS (FIXD MOUNTED DESIGNED)
RATED CURRENT  1650A
RATED PAEK  WITHSTAND CURRENT (Ipk) 
 176 KA 
RATED SHORT-TIME WITHSTAND 
CURRENT (Icw)   80 KA, 1s
 
VERTICAL BUS BARS FOR WITHDRAWABLE
UNIT DESIGNED
RATED CURRENT  900A
RATED PAEK WITHSTAND 
CURRENT (Ipk) 163 KA 
RATED SHORT-TIME WITHSTAND 
CURRENT (Icw)   65 KA, 1s
RATED SHORT-TIME WITHSTAND 
CURRENT (Icw)   50 KA, 3s